FilterGuard 206
| Dust Filter Monitoring
Application
The ADOS Filter-Guard 206
in combination with an evaluation unit continuously monitors the clean air side of any fine dust filter installation.
A warning is initiated when a sudden increase in dust concentration is present, i.e. due to a breakdown in the filter casing or bag.
Measurement range is 0–100 % dust.
Measurement range value – total dust:
0,1 – 20 mg/m
3
0,1 – 50 mg/m
3
0,1 – 100 mg/m
3
Fields of Application
Monitoring fine dust filter systems at the clean air side
Vibrating and jet filter systems
Air extraction installations in wood and plastic processing plants
Air conditioning units with dust filter systems
Paint and varnish production
Ambient air monitoring at workplaces
and many more
Features
Suitable for various types of dust
4-20mA standard output signal
LON
®
interface (optional)
Low current consumption
Robust aluminium housing
Straightforward installation
Easy exchange of the sensor elements
Detectable Types of Dust
Dry dusts:
Wood dust
Household dust
Colouring pigments
Plastic dust
Flour dust
Metallic dust
Mineral dust
and many more
Evaluation Units
Multi-channel installations:
MWS 897
MWS 903
LON
®
-Center 2000
GW 399
Multitronik MC 602
Accessories
Signal horns, warning lamps, warning banners, air control accessories, metering units, plotters, data-logger.
Further accessories can be supplied on request, according to the proposed measurement tasks.
Technical Data
Measurement principle:
optical light dispersion
Fields of application:
filtermonitoring for dry, not sticking, not lumping, not hygroscopic substances
Measurement ranges:
0 – 100 % dust
approx. measurement range:
total dust
0,1 – 20 mg/m
3
0,1 – 50 mg/m
3
0,1 – 100 mg/m
3
dependant on the kind of dust at the measuring point
Medium humidity:
dry
Measurement
accuracy:
pure warning function, no metering unit
Ambient temperature:
-10 °C to +50 °C
Response time (t
90
):
< 10 s
Installation:
flexible flange for output air channel construction
(flat and round channels)
Protection class:
IP 54
Output signals:
analog output 4 (0)–20 mA
RS 485 / LON
®
Voltage supply:
24 V=
Power consumption:
3 VA
Dimensions
(D x L):
50 x 300 mm or
50 x 600 mm (long version)
Weight:
approx. 0,95 kg
Trademark right:
EU-patent
Product data sheet
Filter-Guard 206